0433 597 205

AIR SYSTEMS / PROJECT EXPERIENCE

Fan + Duct System Investigation

Measured system behaviour did not align with the expected fan duty, indicating that the fan, branches, dampers and connected duct resistance needed to be assessed as one network.

WHAT THE OPERATING POINT MEANS

A fan does not have one duty. It operates where its characteristic curve meets the resistance of the connected system.

Measured flow and pressure did not sit on the catalogue duty. Ducts, fittings, branches, dampers and equipment losses were scheduled and summed into an as-found system curve, then compared with a balanced condition.

FAN CURVE / SYSTEM RESISTANCEREPRESENTATIVE
FAN CURVEAS-FOUND SYSTEMBALANCED SYSTEMOP 1OP 2VOLUMETRIC FLOW (m³/h)TOTAL PRESSURE (kPa)
LOSS GROUPWHAT IS REVIEWEDWHY IT MATTERS
Straight ductLength, hydraulic diameter, roughnessDistributed friction
Bends + transitionsGeometry and loss coefficientLocal turbulence and separation
Damper + branchesPosition and flow splitBalancing and control loss
Connected equipmentMeasured or supplier pressure dropOften the dominant fixed loss

ENGINEERING DECISION

Balance the network, change a damper or correct a duct restriction before defaulting to a new fan. Fan laws are used only within their valid speed and density range, then checked against measurements and uncertainty.

ANONYMISED PROJECTFIGURES ARE REPRESENTATIVENOT CERTIFIED RESULTS

IQ ENGINEERING GROUP

Bring the problem.
We will say what the job is.